  • UL/CSA/CE /GB (ecc marking) certified (excluding some models)
  • UL listing is pending (excluding some models)
  • 2-circuit double break basic switch with rugged die-cast aluminum case
  • Oil-, water- and dust-proof structure (IP67 protective structure)
  • Wide range of options available: with neon lamp, with LED lamp, built-in gold-plated contacts, with double seal, corrosion-resistant, heat-resistant, cold-resistant, spatter-guarded, connector type, etc
  • Operation position setting indicator (roller lever and roller plunger types)
$155.40 CAD

Azbil

Honeywell/Azbil/Yamatake - General Purpose Compact Limit Switches

General purpose limit switches with robust construction in an extensive range of models, for use in a wide range of applications.

Datasheet (PDF)

Azbil

Honeywell/Azbil/Yamatake - General Purpose Compact Limit Switches

General purpose limit switches with robust construction in an extensive range of models, for use in a wide range of applications.

Datasheet (PDF)

Model: 1LS1-JL
Contact form: 2-circuit double break
Contact type:

Standard load: Silver, rivet
Low current load: Gold-plated silver, rivet

Terminal type: M4 screw (binding head machine screw with toothed washer), DIN 4-pin connector (M12 size), preleaded
Dielectric strength: Between non-continuous terminals: 1,000 Vac, 50/60 Hz for 1 minute (standard operating characteristics type)
600 Vac, 50/60 Hz for 1 minute (roller lever, high sensitivity characteristics type)

Between each terminal and non-live metal part: 2,000 Vac, 50/60 Hz for 1 minute

Between each terminal and ground:
2,000 Vac, 50/60 Hz for 1 minute (only G-type products with ground terminals)

Insulation resistance:
Min. 100 MΩ (by 500 Vdc megger)
Initial contact resistance:
Standard load: Max. 50 mΩ(6 to 8 Vdc, thermal current 1A, voltage drop method)
Low current load: Max. 100 mΩ(6 to 8 Vdo, thermal current 0.1A, voltage drop method)
Connector:  Max. 40 mΩ(excluding fixed resistance such as cable)
Contact voltage/min.current: 24V 10 mA, 12V 20 mA (standard load), 5V 10 mA (low current load)
Rated operating voltage: 120/240 Vac, 30 Vdc
Compliance: NECA C 4508/JIS C 8201-5-1, IEC 60947-5-1